Power Flow Control Solutions for a Modern Grid Using SMART Power Flow Controllers. Kalyan K. Sen
Чтение книги онлайн.

Читать онлайн книгу Power Flow Control Solutions for a Modern Grid Using SMART Power Flow Controllers - Kalyan K. Sen страница 31

СКАЧАТЬ 1-27. Therefore, the Shunt–Shunt Compensator is severely restricted to operate within the first quadrant when used as a PFC. Then the question arises: “Is it possible to design a new PFC that can control the same amount of transmitted power that is controlled by the Shunt–Shunt Compensator and operate within the allowable range of power angles, while the power rating of this new PFC is a fraction of the conventional Shunt–Shunt Compensator?” For the same example of increasing the power flow in the line from its natural flow of 800 MVA to 1000 MVA, the rating of each of the two units of the Shunt–Series Compensator might be only 200 MVA, resulting in a saving of 80% of the power rating, compared to a Shunt–Shunt Compensator.

Schematic illustration of ranges of Qr versus Pr at the receiving end of the transmission line.

      In an alternate approach to the Shunt–Shunt compensation, the same active and reactive power flows (Pr and Qr) can be obtained using a PFC with a Shunt–Series configuration that applies a series‐compensating voltage (images), such that

      (2‐94b)equation

      or when δs = 0°,

equation

      where the phase‐shift angle,

       (2‐51b) equation

      or

      The magnitude (Vs′s) and the relative phase angle (β) of the series‐compensating voltage (Vs′s) are

      (2‐100)equation

      and

      (2‐101)equation

      For a Shunt–Shunt Compensator, the relationship between the active and reactive power flows (Pr and Qr) at the receiving end is shown by a quarter circle, the radius (a′) of which is varied within the upper and lower limits by the modified sending‐end voltage (Vs′) as shown in Figure 1-27. The relationship is given by the following equation:

      where

      (2‐61)equation

      For a Shunt–Series Compensator, the relationship between active and reactive power flows (Pr and Qr) at the receiving end is shown by the small circle in Figure 1-27 and is given by the following equation:

      where Prn and Qrn are the natural active and reactive power flows at the receiving end of the line and

Schematic illustration of independent active and reactive power flow controller with local reactive power compensation using a Shunt–Series Compensator-based UPFC.

      The Shunt–Series Compensator connects a compensating voltage in series with the line at any relative phase angle in the range of 0°β ≤ 360° with respect to the line voltage at the POC. Figure 1-27 shows that a series‐compensating voltage of 0.2 pu modifies the power angle by 11.54°, which may be near the allowable limit. The most important and unique feature of the Shunt–Series configuration СКАЧАТЬ