Power Flow Control Solutions for a Modern Grid Using SMART Power Flow Controllers. Kalyan K. Sen
Чтение книги онлайн.

Читать онлайн книгу Power Flow Control Solutions for a Modern Grid Using SMART Power Flow Controllers - Kalyan K. Sen страница 25

СКАЧАТЬ a capacitor. A TCSC or SSSC modifies the magnitude and phase angle of the line voltage, which are the combined functionalities of a VR and a PAR as shown in Figure 2‐28. Since, the series reactance compensation technique does not change the effective line resistance, it cannot control the active and reactive power flows in the line independently as shown in Figure 1‐30.

      In a lightly loaded line, the reactive power absorbed by the series reactance of the line may be much less in comparison to the reactive power generated by the line‐to‐ground, shunt capacitance of the line. The resulting voltage increase in the line may reach or exceed the allowable limits for other loads that are connected to the grid. In a heavily loaded transmission line, the reactive power needed by the series reactance of the line may be much more in comparison to the reactive power generated by the shunt capacitance of the line. The resulting voltage along the line may decrease to a point that is below an acceptable limit when the full performance of the load is not possible. If the voltage along the transmission line is increased to be regulated at its nominal value by using a VR, the active power flow increases over the natural flow as discussed in Chapter 2, Section 2.6.1 (Shunt‐Compensating Reactance). If the phase angle between the voltages at the two ends of the transmission line is increased by using a PAR, the active power flow also increases. The unintended consequence of increasing active power flow by voltage regulation or phase angle regulation is that the reactive power flow in the line is also affected. When the line reactance is regulated, both the active and reactive power flows in the transmission line are varied simultaneously.

      If the reactive power along the line is reduced, the freed‐up capacity of the line can be used to increase the revenue‐generating active power flow. As a result, the connected‐generators will be required to supply less reactive power. Furthermore, the efficiencies of the generators and step‐up transformers under a reduced reactive power condition will also increase. Since the loss in the line decreases due to less reactive power flow, the grid becomes more efficient. Therefore, it is desirable to compensate the lines to operate under independent, not simultaneous, control of the active and reactive power flows so that the line can facilitate the delivery of active power with the greatest value. The active and reactive power flows in a line can be regulated independently with a UPFC or an ST that controls the effective impedance of the line between its two ends, which is functionally equivalent to regulating both the magnitude and phase angle of the line voltage simultaneously.

Schematic illustration of response time of the first commercial STATCON for 100 Mvar capacitive step (left) and 100 Mvar inductive step (right). Schematic illustration of voltage profile without an SVC (left) and with an SVC (right).

      However, the fast response from a VSC may be just the right solution to address various issues in addition to var compensation, such as

       Unbalanced voltage

       Harmonic voltage and current

       Voltage spikes

       Voltage flicker.

Schematic illustration of a single-line diagram of an electric arc furnace. СКАЧАТЬ