Название: Alternative Liquid Dielectrics for High Voltage Transformer Insulation Systems
Автор: Группа авторов
Издательство: John Wiley & Sons Limited
Жанр: Физика
isbn: 9781119800187
isbn:
Table 2.7 Doernenburg gas ratio method.
Key gases | Minimum concentration L1 (ppm) |
---|---|
Hydrogen (H2) | 100 |
Methane (CH4) | 120 |
Carbon monoxide (CO) | 350 |
Acetylene (C2H2) | 1 |
Ethylene (C2H4) | 50 |
Ethane (C2H6) | 65 |
Table 2.8 Types of faults by Doernenburg ratio method.
No. | Type of fault | R1 | R2 | R3 | R4 |
---|---|---|---|---|---|
1 | No fault | Conc. (H2 or CH4 or C2H2 or C2H4)>2L1 and Conc. (C2H6 and CO) <L1] or [Conc. (H2 or CH4 or C2H2 or C2H4)< 2L1] | |||
2 | Thermal decomposition | R1 > 1 | R2 < 0.75 | R3 < 0.3 | R4 > 0.4 |
3 | Low‐intensity partial discharge | R1 < 0.1 | R2 = ND | R3 < 0.3 | R4 > 0.4 |
4 | High‐intensity arcing | 0.1 < R1 < 1 | R2 > 0.75 | R3 > 0.3 | R4 < 0.4 |
2.6.1.3 Rogers Ratio Method
In this technique, three gas ratios R1, R2, and R5 are used for the explanation of the incipient faults in a transformer. The boundaries of the gas ratios suggesting a specific fault type is given in Table 2.9. Rogers method is not dependent on specific gas concentrations for the analysis to be valid. This technique is not always suitable as the accuracy is not very good in identifying faults.
2.6.1.4 Duval’s Triangle
The Duval Triangle uses three hydrocarbon gases only, namely methane (CH4), ethylene (C2H4), and acetylene (C2H2), to detect the fault types [75, 76]. The concentration of the gases is plotted in a triangular coordinate system. The types of faults detected by the Duval’s triangle method are given in Table 2.10. The coordinates of the fault are denoted by the points A1=%p1, A2=%p2, A3=%p3 for the percentage concentration of CH4, C2H4, and C2H2 gases, respectively. The concentration of gases in ppm are considered for CH4 = p1, C2H4 = p2, and C2H2 = p3 and are converted to triangular coordinates. The relative proportion of the three gases is calculated as below:
(2.18)
Table 2.9 Types of faults by Rogers ratio method.
No. | Type of fault | R1 | R5 | R2 |
---|---|---|---|---|
1 | No fault | 0.1 < R1 < 1 | R5 < 1 | R2 < 0.1 |
2 | Partial Discharge with low energy density | R1 < 0.1 | R5 < 1 | R2 < 0.1 |
3 | Arcing with high energy discharge | 0.1 ≤ R1 ≤ 1 | R5 > 3 | 0.1 ≤ R2 ≤ 3 |
4 | Low temperature thermal faults | 0.1 < R1 < 1 | 1 ≤ R5 ≤ 3 | R2 < 0.1 |
5 | Thermal faults of temperatures < 700 °C | R1 > 1 | 1 ≤ R5 ≤ 3 | R2 < 0.1 |
6 | Thermal faults of temperatures >700 °C | R1 > 1 | R5 > 3 | R2 < 0.1 |
Table 2.10 Types of faults.
No. | Type of fault | Symbol |
---|---|---|
1 | Partial discharge with low energy density | PD |
2 |
Discharge (arc) with
СКАЧАТЬ
|