Figure 1.10 Superstructure of SOFC – CO2 capture process configurations.
Source: Adams et al. [40].
One example of an MCFC and CO2 capture system was developed by Fuel Cell Energy (FCE), namely, the Combined Electric Power and Carbon‐dioxide Separation (CEPACS). In the process of capturing >90% CO2. In this configuration, the system can generate up to 351 MWe additional power (net AC), after compensating for the auxiliary power requirements of CO2 capture and compression.5
1.3 Integration of Post‐combustion CO2 Capture in the Power Plant and Electricity Grid
A key aspect of thermal power plants is their carbon intensity (CO2 emitted per unit of energy generated, generally expressed as kg CO2/MWh). Nowadays, the global average is around 500 kgCO2/MWh, which must be reduced to 100 kgCO2/MWh by the late 2030s to be consistent with a 2 °C climate pathway [36]. Even if combined cycle thermal power plants can be considered as low carbon alternatives in some scenarios, in the mid‐to‐long term, it might be required to further decarbonize the existing units by retrofitting them with CCS or by building novel designs with low CO2 emissions. As demonstrated at commercial scale, post‐combustion CO2 capture can significantly reduce the carbon intensity of thermal power plants [2]. Table 1.3 compares the carbon intensity of thermal power plants with and without CCS.
1.3.1 Integration of the Capture Unit in the Thermal Power Plant
In principle, the key integration aspects of the power plant and the capture unit are the flue gas, emitted by the power plant and sent to the capture unit, and the energy requirements of the chemical absorption/desorption process, provided by the power plant to the capture unit (Figure 1.11). Figure 1.11 shows a simplified schematic of a power plant integrated with a post‐combustion CO2 capture system. The main energy and mass integration flows are described. Fuel and air are used in the combustion process, providing heat to produce steam in the power cycle. The flue gas from the combustion is sent to the CO2 capture unit and leaves it lean in CO2. A CO2 rich stream is produced in the CO2 capture plant and sent to conditioning, transport, and storage. Heat in the form of steam is provided from the power plant and is returned back as water condensate. Electricity from the power plant is utilized to run the auxiliary systems of the capture unit, including the flue gas fan, cooling, and solvent circulation pumps. Higher levels of process integration between the power plant and the capture unit can be considered, as explained in [41].
Table 1.3 Low heat value (LHV) efficiency, carbon intensity, and energy penalty in coal‐ and gas‐based thermal power plants with CCS [43, 54, 76].
Source: Adapted from Adams and Mac Dowell [43], Gonzalez‐Salazar et al. [54], Kvamsdal et al. [76].
Carbon intensity (kg CO2/MWh) | LHV efficiency (%) | Efficiency reduction (%) | |
---|---|---|---|
Pulverized coal subcritical | 700–1000 | 30–47 | — |
Combined cycle | 350–450 | 56–62 | — |
Pulverized coal with CCS at 90% capture rate | 130 | 25–42 | 5–7 |
Combined cycle with CCS at 90% capture rate | 40–50 | 50–54 | 6–8 |
Figure 1.11 Schematic integration of a power plant with a post‐combustion CO2 capture system.
The energy required to run the chemical absorption–desorption process in the capture unit process is mainly due to the (i) mechanical work to drive the flue gas fan to compensate the pressure drop induced by direct contact cooler, absorber column, and water wash sections and ducting; (ii) mechanical work to drive the pumps for cooling water and solvent circulation pumps; (iii) steam for solvent reclaiming because of its degradation in order to keep the solvent fresh and contaminant free; and (iv) steam to feed the reboiler duty: regenerate the solvent, generate stripping vapors, heat up the solvent to saturation conditions, and evaporate the water.
The flue gas is sent to the capture unit and additional pressure drop is imposed, which is a function of the thermal power plant unit, its equipment for emissions control, and the boiler type. In gas plants, the heat recovery steam generator in the exhaust gas generally imposes the additional pressure drop downstream the gas turbine (in the order of 20–40 mbar [8]), and in boilers (coal/oil/gas fired), a fan is commonly used to keep it under slightly sub‐ambient pressure. The main flue gas line equipment inducing pressure drop would be as follows [42]:
The particle removal system (electrostatic precipitator [ESP]).
The flue gas desulfurization (FGD) unit (if existing).
The NOx scrubber (if required) 2–7 mbar [42].
The bypass stack and damper if installed to bypass the capture unit.
Flue gas recirculation ducting and/or bypass (if utilized).
Direct contact cooler, absorber column, and water washes 6–80 mbar [43].
Absorber duct and stack.
In general, a fan will be required to overcome those pressure drops, whose size will depend on the volumetric flow and pressure drop. In combined cycle thermal power plants, most of the pressure drop might be overcome by raising the back pressure of the gas turbine. However, in boilers, the pressure drop is generally overcome by one or more fans [43].
The extraction of steam from the power plant steam turbine could cover the requirements in the capture system. This strategy will reduce the power output at a lower degree than the amount of heat extracted because the exergy content of the steam is just a fraction of the heat [41]. When the extracted steam is superheated (typically at higher steam pressure), it СКАЧАТЬ